Just reached out to AC Infinity. They said that the unit draws 800watts on 120volt so 800 divided by 120 then multiply that by1.25= 8.33333amps to run your unit. Any standard 15amp dedicated circuit should work to run it
krommm and fraughturnip8 -
Is your basement on a dedicated circuit? Is that circuit controlled by a GFCI/AFCI combo breaker or an actual GFCI outlet? Go to your panel and see. Each breaker should be labeled. Take a couple pictures and post. I could try and recommend a solution with more info
krommm -
So GFCI outlets will trip with too much load. That’s why they recommend not plugging fridges or freezers into them. When the compressor engages the load could trip the GFCI. You could replace the GFCI with a regular outlet. How many outlets are connected to the GFCI?